DE-VX 4200F

DE-VX 4210F (10" Display)

Since January 2018 our successful variable control system VX-4100 has been replaced by the technically new  VX-4200F . Technical innovation concerning the hardware (e.g. CPU, memory) as well as modified technical connections (network, interfaces) are taken into consideration. Of course, all devices are compatible to current and former demig-device-generations.

The two display types 10″ and 15″ – together with the high-performance CPU enables a fast screen refresh and a comfortable user interface. A complex and graphical presentation of schematic diagrams is possible. For an optimal installation, all models are designed as flat version now. Adaption frames enables modernizations without changing the switch cabinet cutouts.

DE-VX 4215F (15" Display)


Operation

  • Easy menu-driven operation by keyboard and programmable special keys
  • Process orientated programming
  • Menu selectable operating language
  • Individual configuration possibilities for the OEM

 

Technical facts

  • Comfortable process visualization with high-resolution 10“ or 15″ color display
  • Quick reaction time at controlling and image composition by Intel Atom Processor
  • Networkable by Gigabit Ethernet
  • CAN-Bus and Profibus (Slave/Master) connection possible
  • Telemaintenance via modem for monitoring and maintenance
  • Hardware-Watchdog for digital and analog outputs as well as for the complete system
  • Switch panel housing with front seal protection class IP65

 

Data recording

  • Recording of all process variables
  • Integrated recording functions
  • Graphic and numeric data output
  • Print functions
  • Quality proof according to DIN ISO 9000


Regulation

  • Multi-system regulation
  • All standard regulation algorithms with  parameter switch-over and set point correction
  • Special functions (e.g. diffusion control, F-value calculation)   


Control

  • Integrated PLC (S5© and S7© compatible)
  • Manual operation mode
  • Step sequence control
  • Special functions (e.g.  impulse firing system)

 

Visualization

  • Process view(s) with real-time status
  • Alarm- and message view with help function
  • Online view of process variables, numeric and as trend display


System computer unit

  • Industrial computer system equipped with a high-powered processor
  • Integrated PLC, S5© and S7© compatible instruction set, max. program length: 60.000 instructions with time requirement for 1.000 bit instructions at < 0,2ms, up to 256 timer, 1024 messages, 1024 alarms (optional on delay)


Memory

  • 2 GB RAM working memory
  • 8 GB Flash for operating program and configuration storage
  • 4 MB SRAM (battery-buffered for current process status store, treatment programs and measurement recording)


Interfaces/Connections

All interfaces (incl. USB) are electrically isolated from the supply and system potential.

  • COM1 DIN-RS232 (electrically isolated)
  • COM2 DIN-RS232/RS422/RS485 (electrically isolated with software controlled termination)
  • COM3 DIN-RS232/RS422/RS485 (electrically isolated with software controlled termination)
  • 4 USB-interfaces (electrically isolated) for external keyboard, mouse, printer, etc.
  • 1 X Gigabit Ethernet interface, TCP/IP protocol for configuration, remote control, supervisory system connection, Modbus/TCP, Auto MDI-X
  • Protocols, e.g. RK 512, Modbus, 3964R
  • Can-Bus for the connection of external modules
  • Power supply input voltage range from 110V AC up to 230V AC, 50-63Hz
  • Profibus- DP- Slave (optional) (EN 50 170/DIN 19245 part 1) 9,6 Kbit/s -12Mbit/s, automatic bit rate recognition, E/A RS 485 cabling, DSUB- 9- plug connector, electrically isolated. Max. 244 bytes input and output data
  • Profibus- DP- Master (optional) (EN 50 170/DIN 19245 part 1) for the connection of up to 125 Slaves, 9,6 Kbit/s – 12Mbit/s, automatic bit rate recognition, E/A RS 485 cabling, DSUB- 9- plug connector, electrically isolated. Max. 512 bytes input and output data. Configuration via external PC software (separate order necessary)



Display

  • 10,4″ TFT LCD-colour display with extra wide viewing angle, XGA resolution (1024×768 pixels)
  • 15“ TFT LCD-colour display with extra wide viewing angle, XGA resolution (1024×768 pixels)
  • Standard VGA-interface for additional monitor


Operation

  • Membrane keyboard (according to DIN EN 60529, IP protection 65) with alpha key functionality
  • Externally connectable USB keyboard
  • Externally connectable USB mouse
  • Programmable special keys
  • Unicode-language support
  • Multiple language switch at runtime


Security

  • Dual security functions by global and local watchdog functions
  • Power failure monitoring
  • Copy and know-how protection


Installation

  • Front panel with integrated seal IP65
  • Ambient temperature 0…+45°C
  • Relative humidity 0…90% non-condensing at +40°C and under 3000m
  • Storing temperature -20…+60°C
  • Overvoltage category III (nach DIN EN 60664-1)
  • Soiling stage 2 (nach DIN EN 60664-1)


Inputs/Outputs (max. expansion indicated)

                                                              Internal:                       incl. CAN Bus:

  • Analog inputs:                                128                                 128
  • Analog outputs:                                64                                   96
  • Digital inputs:                                 256                                 512
  • Digital outputs:                               256                                 512


Programmer/Controller (max. expansion indicated)

  • Set points:          192
  • Control tracks:   512
  • Control loops: 1.024
  • Limit values:   1.024
  • Alarms:           1.024 (on delay) with alarm history
  • Installations:          8 independent installations configurable
  • Recorder:           64 process variables recordable

k

Technical data I/O cards

Part

DescriptionPart.-Nr.

AD8

DA8

AD 4/DA 2

AD 4/DA 2G

IN 32

OUT 32

IN24 /OUT 16

8-fold-analog input card (max. 64 inputs)

8-fold-analog output card (resolution 12 Bit)

4-fold IN/2-fold OUT analog combi

4-fold IN/2-fold OUT analog combi (with comparator)

32-fold-digital input card

32-fold-digital output card (Transistor)

24-fold-digital IN / 16-fold-digital OUT card (Transistor)

601613

601615

601614

601616

601611

601612

601608



AD8: 8-fold-analog input card (part number: 601613)

  • Each input electrically isolated from the other and from the system potential
  • DC measuring possible
  • Inputs configurable: 0…100mV 0…500mV
  • 0…2V 0…10V
  • 0…20mA
  • 0…400 Ω (2/3/4-wire technique)
  • Error < 0.1% from measuring range
  • Free combination of input types
  • Min. measurement duration per channel 20ms
  • Double coldjunction temperature measurement in connector

For the following thermocouples a linearization is included:

  • Cu-CuNi Typ U ( -200 … +600 °C)
  • Fe-CuNi Typ L ( -200 … +900 °C)
  • NiCr-CuNi Typ E ( 0 … +1000 °C)
  • Ni-CrNi Typ K ( -200 … +1370 °C)
  • PtRh-AuPdPt ( -100 … +1300 °C)
  • PtRh13-Pt Typ R ( 0 … +1740 °C)
  • PtRh10-Pt Typ S ( 0 … +1760 °C)
  • PtRh30-PtRh6 Typ B ( 0 … +1800 °C)
  • WRe3-WRe25 ( 0 … +2400 °C)
  • WRe3-WRe26 ( 0 … +2500 °C)
  • NiCrSi-NiSi Typ N ( -270 … +1400 °C)
  • and Pt 100 ( -200 … +800 °C)


DA8: 8-fold-analog output card (resolution 12 Bit) (part number: 601615)

  • All outputs are electrically isolated from the system potential
  • Outputs: 0…10V load >= 1k Ω
  • 0(4)…20mA  burden <= 1000 Ω
  • Resolution 12 Bit/0.025%
  • Output rate depending on configuration (min. every 100ms)
  • Local watchdog function integrated


AD4/DA2: 4-fold IN/2-fold OUT analog combi (part number: 601614)

Analog inputs (4):

  • Each input is electrically isolated from the other and from the system potential
  • DC measuring possible
  • Inputs configurable: 0…100mV 0…500mV
  • 0…2V 0…10V
  • 0…20mA
  • 0…400 Ω (2/3/4-wire technique)Error < 0.1% from measuring range
  • Free combination of input types
  • Min. measurement duration per channel 20ms
  • Coldjunction temperature measurement in connector

For the following thermocouples a linearization is included:

  • Cu-CuNi Typ U ( -200 … +600 °C)
  • Fe-CuNi Typ L ( -200 … +900 °C)
  • NiCr-CuNi Typ E ( 0 … +1000 °C)
  • Ni-CrNi Typ K ( -200 … +1370 °C)
  • PtRh-AuPdPt ( -100 … +1300 °C)
  • PtRh13-Pt Typ R ( 0 … +1740 °C)
  • PtRh10-Pt Typ S ( 0 … +1760 °C)
  • PtRh30-PtRh6 Typ B ( 0 … +1800 °C)
  • WRe3-WRe25 ( 0 … +2400 °C)
  • WRe3-WRe26 ( 0 … +2500 °C)
  • NiCrSi-NiSi Typ N ( -270 … +1400 °C)
  • and Pt 100 ( -200 … +800 °C)


Analog outputs (2):

  • All outputs are electrically isolated from the system potential
  • Outputs: 0…10V load>=1k Ω
  • 0(4)…20mA  burden<= 500 Ω
  • Resolution12 Bit/ 0.025%
  • Output rate depending on configuration (min. every 100ms)
  • Local watchdog function integrated


AD4/DA2: 4-fold IN/2-fold OUT analog combi (with comparator) (part number: 601616)

as articel 601614 with the following extension

Comparator inputs (2):

  • The both inputs 0…10V are positioned on the potential of the analog outputs and they are compared with each other
  • Relay isolated comparator output switches depending on the comparator´s result


IN32: 32-fold-digital input card (part number: 601611)

  • All inputs are electrically isolated by optocoupler from system potential
  • Input potentials 0 V…30V (DC);  low signal 0 < 5V high signal 1 > 15V
  • Hardware debouncing of each input, signal length 1,6 ms/0,14ms
    (different signal length possible on request)



OUT32: 32-fold-digital output card (Transistor) (part number: 601612)

  • All outputs are electrically isolated by optocoupler from system potential
  • Relay contacts load max. 30V / max. 0,5A / max. 12W (ohmic load)
  • External voltage supply of the output relays 24V DC ± 15%
  • Local wachtchdog function integrated



IN24/OUT16: 24-fold-digital IN / 16-fold-digital OUT card (Transistor) (part number: 601608)

  • All inputs are electrically isolated by optocoupler from system potential
  • Input potentials 0 V…30V (DC) 15mA; low signal 0 < 5V high signal 1 > 15V
  • Hardware debouncing of each input, min. signal length 200ms (different signal length possible on request)
  • All outputs with nominal load for each 0,5A (All outputs may be switched at the same time)
  • Outputs are short circuit protected
  • Electric current supply 18VDC.36VDC
  • Local wachtchdog function integrated
  • Outputs switched off when supply < 16V

Technical Data distributed I/O

Article

Description

Part-No

AD4/DA2 GM

AD4/DA2

I/O16 GM  

I/O16

4-fold IN/2-fold OUT analog combi group master 

4-fold IN/2-fold OUT analog combi extension

16-fold variable digital I/O combi group master

16-fold variable digital I/O combi extension

 602918

602919 

602916

602917

 

Group Master Modul with 4 analog inputs and 2 analog outputs (Part number: 602918)

Analog inputs (4):

  • Each input electrically isolated from the other and from the system potential
  • DC measuring possible
  • Inputs configurable: 0…100mV 0…500mV
  • 0…2V, 0…10V, 0…20mA
  • 0…400 Ω (2/3/4-wire technique)
  • Error < 0.1% from measuring range
  • Free combination of input types by the configuration software
  • Scanning interval 120ms x (number of assignet inputs)= 120ms bis 480ms
  • Coldjunction temperature 0°C .. 100°C (input AD1, AD3)

For the following thermocouples a linearization is included:

  • Cu-CuNi Typ U ( -200 … +600 °C)
  • Fe-CuNi Typ L ( -200 … +900 °C)
  • NiCr-CuNi Typ E ( 0 … +1000 °C)
  • Ni-CrNi Typ K ( -200 … +1370 °C)
  • PtRh-AuPdPt ( -100 … +1300 °C)
  • PtRh13-Pt Typ R ( 0 … +1740 °C)
  • PtRh10-Pt Typ S ( 0 … +1760 °C)
  • PtRh30-PtRh6 Typ B ( 0 … +1800 °C)
  • WRe3-WRe25 ( 0 … +2400 °C)
  • WRe3-WRe26 ( 0 … +2500 °C)
  • NiCrSi-NiSi Typ N ( -270 … +1400 °C)
  • Pt 100 ( -200 … +800 °C)

Analog outputs (2):

  • All outputs are electrically isolated from the system potential
  • Outputs: 0…10V load >=10k Ω
  • 0(4)…20mA burden< = 600 Ω
  • Resolution 12 Bit/0.025%
  • Output rate depending on configuration (min. every 100ms)
  • Local watchdog function integrated


Extension Modul with 4 analog inputs and 2 analog outputs (Part number: 602919)

Analog inputs (4):

  • Each input electrically isolated from the other and from the system potential
  • DC measuring possible
  • Inputs configurable: 0…100mV 0…500mV
  • 0…2V, 0…10V, 0…20mA
  • 0…400 Ω (2/3/4-wire technique)
  • Error < 0.1% from measuring range
  • Free combination of input types by the configuration software
  • Scanning interval 120ms x (number of assignet inputs)= 120ms bis 480ms
  • Coldjunction temperature 0°C .. 100°C (input AD1, AD3)

For the following thermocouples a linearization is included:

  • Cu-CuNi Typ U ( -200 … +600 °C)
  • Fe-CuNi Typ L ( -200 … +900 °C)
  • NiCr-CuNi Typ E ( 0 … +1000 °C)
  • Ni-CrNi Typ K ( -200 … +1370 °C)
  • PtRh-AuPdPt ( -100 … +1300 °C)
  • PtRh13-Pt Typ R ( 0 … +1740 °C)
  • PtRh10-Pt Typ S ( 0 … +1760 °C)
  • PtRh30-PtRh6 Typ B ( 0 … +1800 °C)
  • WRe3-WRe25 ( 0 … +2400 °C)
  • WRe3-WRe26 ( 0 … +2500 °C)
  • NiCrSi-NiSi Typ N ( -270 … +1400 °C)
  • Pt 100 ( -200 … +800 °C)

Analog outputs (2):

  • All outputs are electrically isolated from the system potential
  • Outputs: 0…10V load >=10k Ω
  • 0(4)…20mA burden< = 600 Ω
  • Resolution 12 Bit/0.025%
  • Output rate depending on configuration (min. every 100ms)
  • Local watchdog function integrated

 



Group Master Modul with 16 digital inputs or outputs (Part number: 602916)

  • The contacts 0.0-1.7 may be configured bit by bit as inputs or outputs
  • Configured as output: max . load 2A per output at 18V .. 36V
  • Configured as input: Input potentials 0 V…30V (DC) 15mA; logic 0 < 6V logic 1 > 10V


Extension Modul with 16 digital inputs or outputs (Part number: 602917)

  • The contacts 0.0-1.7 may be configured bit by bit as inputs or outputs
  • Configured as output: max . load 2A per output at 18V .. 36V
  • Configured as input: Input potentials 0 V…30V (DC) 15mA; logic 0 < 6V logic 1 > 10V


Measurements DE-VX 4210F

  • Installation depth:                  350mm, max. wall thickness 6mm
  • Cut-out dimensions:              382mm x 217mm (WxH)
  • Front panel dimensions:       400mm x 235mm x 4mm (WxHxD)

 

Measurements DE-VX 4215F

  • Installation depth:                350mm, max. wall thickness 6mm
  • Cut-out dimensions:            500mm x 315mm (WxH)
  • Front panel dimensions:      550mm x  335mm x 4mm (WxHxD)

  

Brochures

DE-VX 4200dt.pdf

DE-VX 4200eng.pdf

 
Technical data

DE-VX 4200F_dt.pdf

DE-VX 4200F_eng.pdf

I/O Karten_dt.pdf

I/O cards_eng.pdf

DezentrPeripherie_dt.pdf

Distributed I/O_eng.pdf

V18-03-001

V18-03-001

V16-08-001

V16-0-8001

V16-10-001

V16-10-001

Manuals

DE-VX 4200_dt.pdf

DE-VX 4200_eng.pdf

ab Vers. 12.14.0_2018

from Vers. 12.14.0_2018

Installation advices

Pinbelegung_dt.pdf

Pin assignment_eng.pdf

Adresskonfig Karten_dt.pdf

Adress config cards_eng.pdf

V18-01-001

V18-01-001

V16-02-002

V16-02-002

Controller program updates